Effect of server load variation on rack air flow distribution in a raised floor data center
Author
Kumar, Pramod ; Sundaralingam, Vikneshan ; Joshi, Yogendra
Author_Institution
CEETHERM Data Center Lab., Georgia Inst. of Technol., Atlanta, GA, USA
fYear
2011
fDate
20-24 March 2011
Firstpage
90
Lastpage
96
Abstract
This paper presents experimental studies on server level rack air distribution for a preset perforated tile air flow rate. A series of experiments are performed using a 22.8 kW server simulator placed in a raised floor data center facility. The rack air flow rate is varied by adjusting the fan speed of the server simulator. Particle Image Velocimetry (PIV) technique is used to capture the air flow pattern at various locations in the cold aisle at the inlet of the server simulator. The PIV images are recorded at various locations and later combined to get the complete air distribution map across the rack inlet. Various cases of rack air flow distributions are investigated by varying the server simulator fan speed settings for given perforated tile air flow rate. A significant change in the air distribution pattern is observed for various cases investigated.
Keywords
aerodynamics; computer centres; cooling; fans; flow visualisation; network servers; air distribution pattern; air flow pattern; particle image velocimetry; power 22.8 kW; preset perforated tile air flow rate; rack air flow distribution; raised floor data center facility; server load variation; server simulator; Cameras; Floors; Fluid flow measurement; Load management; Servers; Tiles; Velocity measurement; PIV; Rack air flow distribution; Server Simulator;
fLanguage
English
Publisher
ieee
Conference_Titel
Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), 2011 27th Annual IEEE
Conference_Location
San Jose, CA
ISSN
1065-2221
Print_ISBN
978-1-61284-740-5
Type
conf
DOI
10.1109/STHERM.2011.5767184
Filename
5767184
Link To Document