A calculation of transient overvoltage for rationalization of insulation design of 22 kV cable system
Author
Oka, Keisuke ; Hirai, Takao ; Murata, Koichi ; Hashimoto, Eiji ; Ariga, Yasuo
Author_Institution
Tokyo Electr. Power Co. Inc., Japan
Volume
2
fYear
2002
fDate
6-10 Oct. 2002
Firstpage
1247
Abstract
This paper presents a new approach for a reduction of test voltage for power distribution equipment of 22 kV cable system. EMTP calculations are used in this examination for rationalization of insulation design of 22 kV cable system. From the result of parameter analysis by the typical model of 22 kV cable system, the system condition of distribution line that causes the largest transient overvoltage is determined. In the case of switching surge, there is little relationship between neutral resistance and the overvoltage, and then the maximum per unit value of abnormal voltage is approximately 2 pu. On the other side, in the case of fault surge, the overvoltage increases as the neutral resistance increases, and then the maximum per unit value of the abnormal voltage becomes 2.68 pu. According to the above results, the conventional test voltage for 22 kV distribution equipment could be reduced by approximately 20%.
Keywords
EMTP; overvoltage; power cable insulation; power cable testing; power system transients; surges; switching; 22 kV; EMTP; Electromagnetic Transient Program; abnormal voltage; distribution line; fault surge; insulation design; neutral resistance; parameter analysis; power distribution equipment; switching surge; transient overvoltage calculation; Cable insulation; EMTP; Power cable insulation; Power cables; Power distribution; Power system modeling; Power system transients; Surges; System testing; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
Print_ISBN
0-7803-7525-4
Type
conf
DOI
10.1109/TDC.2002.1177657
Filename
1177657
Link To Document