• DocumentCode
    3162368
  • Title

    Insulator aging tests with HVAC and HVDC excitation using the tracking wheel tester

  • Author

    Holtzhausen, J.P. ; Pieterse, P.J. ; Vermeulen, H.J. ; Limbo, S.

  • Author_Institution
    Dept. Electr. Eng., Stellenbosch Univ., Stellenbosch, South Africa
  • fYear
    2010
  • fDate
    11-14 Oct. 2010
  • Firstpage
    445
  • Lastpage
    448
  • Abstract
    An experimental study was conducted, using a Rotating Wheel Tracking and Erosion Tester (RWT) with the aim to compare the aging performance of different insulators under AC and DC (both polarities) excitation. The procedures of the standard were adapted to perform AC and DC (both polarities) tests on 6 practical insulators from different manufacturers, representing different materials and specific creepage distances. The results obtained confirm the extreme severity of the test, especially for the silicone rubber insulators. The DC tests turned out to be more severe than the AC tests. The formation of a brown deposit on the insulator surface was observed and investigated.
  • Keywords
    HVDC power transmission; flexible AC transmission systems; insulator testing; polymer insulators; silicone rubber insulators; HVAC excitation; HVDC excitation; creepage distances; erosion tester; insulator aging tests; silicone rubber insulators; tracking wheel tester; Degradation; Insulation life; Insulators; Leakage current; Materials; Strontium; Wheels;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application (ICHVE), 2010 International Conference on
  • Conference_Location
    New Orleans, LA
  • Print_ISBN
    978-1-4244-8283-2
  • Type

    conf

  • DOI
    10.1109/ICHVE.2010.5640730
  • Filename
    5640730