    Interaction between test circuit for generation of secondary arcs and short-circuit test transformer

  • Author

    Martins, Helvio ; de Faria Ferreira, C. ; Cerqueira, Walter ; Vasques, Carlos Magno ; Trindade, Mauro

  • Author_Institution
    CEPEL, Electr. Power Res. Center, Brazil
  • fYear
    2010
  • fDate
    11-14 Oct. 2010
  • Firstpage
    361
  • Lastpage
    364
  • Abstract
    This work has its origin from research needed to identify possible damage in a short-circuit test transformer, during experiments for modeling secondary electrical arcs. In some cases the arc had self-extinguished applying a steep wave to the test circuit and its ac source (transformer). Aiming to investigate if there was any interaction between the suspect transformer and testing circuit and its excitations, a research was conducted in laboratory with controlled atmospheric impulse chopped waves, with typical “fall times” for discharges in air. An analysis considering the components of frequency generated by chopped in air, the amplifier factors generated by test circuit (short line + auxiliary transformer), the natural resonance frequencies of the suspect transformer and its frequency components of the BIL showed interesting coincidences that can be extrapolated to real power system conditions.
  • Keywords
    arcs (electric); circuit testing; power transformer testing; short-circuit currents; ac source; discharges; electrical arcs; natural resonance frequencies; power system; short-circuit test; testing circuit; transformer test; Frequency measurement; Frequency response; Impedance; Laboratories; Oil insulation; Power transformer insulation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application (ICHVE), 2010 International Conference on
  • Conference_Location
    New Orleans, LA
  • Print_ISBN
    978-1-4244-8283-2
  • Type

    conf

  • DOI
    10.1109/ICHVE.2010.5640753
  • Filename
    5640753