• DocumentCode
    3185155
  • Title

    Protection testing of a 100% stator ground fault using a phase domain synchronous machine model in real time

  • Author

    Dehkordi, A.B. ; Ouellette, D.S. ; Forsyth, P.A.

  • Author_Institution
    RTDS Technol. Inc., MB, Canada
  • fYear
    2010
  • fDate
    March 29 2010-April 1 2010
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper utilizes a significantly improved phase domain synchronous machine model to test a multi-function relay model created for a real time digital simulator. One of the features of the machine model is its capability of simulating stator internal faults. Third harmonic voltage on the neutral and terminals of the machine and its variation with load and stator-ground faults is accurately represented. This feature makes the machine model a good candidate for testing a "100% stator-ground fault protection scheme" based on the third harmonic voltage. The performance of the relay model for "stator differential protection", "100% stator-ground protection" and the "loss of field excitation protection" schemes is verified and the results are presented in this paper.
  • Keywords
    power system harmonics; power system protection; stators; synchronous machines; multi-function relay model; phase domain synchronous machine model; power system protection; protection testing; real time digital simulator; stator-ground fault protection scheme; third harmonic voltage; protection relay; real-time digital simulation; synchronous generator;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection (DPSP 2010). Managing the Change, 10th IET International Conference on
  • Conference_Location
    Manchester
  • Type

    conf

  • DOI
    10.1049/cp.2010.0234
  • Filename
    5522224