Abstract
An error compensation technique for measuring current transformers is described. An example is shown for current transformers installed in 150 kV switching devices. Initial ratio errors in the order of 4% and phase shifts around 20 min were reduced to 0.1% and 6 min after the compensation.
Keywords
current transformers; electric current measurement; error compensation; high-voltage techniques; 150 kV; current measurement; current transformers; error compensation; high voltage networks; switching devices; Circuits; Current measurement; Current transformers; Energy measurement; Error compensation; Impedance; Intelligent networks; Magnetic analysis; Saturation magnetization; Testing;