    Research on identification between inrush current and internal faults of power transformer based on H-S transform

  • Author

    Jiao, Shangbin ; Huang, Huang

  • Author_Institution
    Dept. of Autom. of Eng., Xi´´An Univ. of Technol., Xi´´An, China
  • Volume
    8
  • fYear
    2010
  • fDate
    16-18 Oct. 2010
  • Firstpage
    3619
  • Lastpage
    3624
  • Abstract
    In order to solve the problem of misoperation of transformer differential relay due to the inrush current, inrush current and internal faults must be discriminate effectively. This paper presents a novel approach by using hyperbolic S-transform (HST) which is a very powerful tool for non-stationary signal analysis giving the information of transient currents both in time and in frequency domains. The signal was transformed to phase space by using HST and the features extracted, the time-frequency contours are obtained after HST, it is found that the time-frequency contours in case of inrush current are different from that in case of internal faults. By calculating the energy and the ratio of energy level 1 and level 9 we found that ratio 6 is the threshold between inrush current and fault current.
  • Keywords
    fault currents; power transformers; time-frequency analysis; transforms; fault current; frequency domains; hyperbolic S-transform; inrush current; internal faults; nonstationary signal analysis; power transformer; time domains; time-frequency contours; transformer differential relay; transient currents; Circuit faults; Fault currents; Harmonic analysis; Surge protection; Surges; Time frequency analysis; Transforms; H-S transform; inrush current; internal faults; transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Image and Signal Processing (CISP), 2010 3rd International Congress on
  • Conference_Location
    Yantai
  • Print_ISBN
    978-1-4244-6513-2
  • Type

    conf

  • DOI
    10.1109/CISP.2010.5646191
  • Filename
    5646191