DocumentCode
3245574
Title
Permittivity matching effects on coil section of oil-immersed transformer
Author
Hikosaka, T. ; Asada, T. ; Miyamoto, M. ; Kousaka, M.
Author_Institution
Lab. of Power Technol., Fuji Electr. Corp. Res. & Dev. Ltd., Chiba, Japan
fYear
1999
fDate
1999
Firstpage
499
Lastpage
502
Abstract
The lightning impulse breakdown voltage of the coil section of oil-immersed transformers is dominated by the partial discharge voltage of the wedge-shaped oil gaps made of the paper insulated conductors, mineral oil, and the coil section spacers. We have studied the permittivity matching effects on the lightning impulse breakdown voltage of the coil section models by means of the experiments and the electric field analyses. The relationship between the critical electric field E in the wedge-shaped oil gap when the breakdown occurred, and the gap length d was acquired. Moreover, the breakdown strength of the coil section models were estimated by using the above relationship within 6% error compared to the measured average values
Keywords
electric breakdown; partial discharges; permittivity; transformer oil; transformers; coil section; coil section spacers; critical electric field; gap length; lightning impulse breakdown voltage; mineral oil; oil-immersed transformer; paper insulated conductors; partial discharge voltage; permittivity matching; wedge-shaped oil gaps; Breakdown voltage; Coils; Conductors; Electric breakdown; Lightning; Oil insulation; Partial discharges; Permittivity; Petroleum; Power transformer insulation;
fLanguage
English
Publisher
ieee
Conference_Titel
Dielectric Liquids, 1999. (ICDL '99) Proceedings of the 1999 IEEE 13th International Conference on
Conference_Location
Nara
Print_ISBN
0-7803-4759-5
Type
conf
DOI
10.1109/ICDL.1999.798981