• DocumentCode
    3248757
  • Title

    Aging of stator bars exposed to end arm discharges

  • Author

    Hudon, C. ; Bélec, M.

  • Author_Institution
    Inst. de Recherche, Hydro-Quebec, Varennes, Que., Canada
  • Volume
    2
  • fYear
    1996
  • fDate
    20-23 Oct 1996
  • Firstpage
    829
  • Abstract
    Three of the most common types of end arm discharges occurring during normal operation of air-cooled hydro-generators have been simulated in the laboratory. Sections of stator bars have been modified to induce either surface tracking, corona discharges at the semi-conductive paint/corona suppressor junction, or bar-to-bar discharges. Two setups of each type of defect were subjected to an aging voltage of 20 kilovolts, and discharge measurements were carried out as a function of time at both 20 kV and 8 kV. Phase resolved partial discharge and spectral analyses made it possible to recognize the activity of specific external defects
  • Keywords
    ageing; corona; hydroelectric generators; partial discharges; stators; 20 kV; 8 kV; aging; air-cooled hydrogenerator; bar-to-bar discharge; corona discharge; end arm discharge; external defect; phase resolved partial discharge; semiconductive paint/corona suppressor junction; spectral analysis; stator bar; surface tracking; Aging; Corona; Laboratories; Paints; Partial discharge measurement; Partial discharges; Stator bars; Surface discharges; Time measurement; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1996., IEEE 1996 Annual Report of the Conference on
  • Conference_Location
    Millbrae, CA
  • Print_ISBN
    0-7803-3580-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.1996.564636
  • Filename
    564636