DocumentCode
3257242
Title
Operating performance analysis on heating conditions of large sewage source heat pump system
Author
Sun Qiong ; Zhao-yi, Zhuang
Author_Institution
Sch. of Municipal & Environ. Technol., Harbin Inst. of Technol., Harbin, China
fYear
2011
fDate
22-24 April 2011
Firstpage
1375
Lastpage
1378
Abstract
This paper obtained the changing range of sewage temperature, the inlet and outlet temperatures of the sewage heat exchanger, evaporator and condenser in winter by monitoring the large sewage source heat pump system in Shi Jia-zhuang. By the testing data, the operating performance of the heat pump system was studied. During the heating test, the heat pump system operated steadily and the coefficient of heat transfer of the sewage heat exchanger was 740 W/ (m2·°C), and the average coefficient of performance of the heat pump was 3.76. These can be taken as references for the design and engineering application of the sewage source heat pump systems.
Keywords
heat exchangers; heat pumps; heat transfer; heating; sewage treatment; Shi Jia-zhuang; condenser; evaporator; heat transfer; heating conditions; sewage heat exchanger; sewage source heat pump system; sewage temperature; Absorption; Heat pumps; Heat transfer; Temperature distribution; Temperature measurement; Water heating; coefficient of heat transfer; coefficient of performance; heat pump; sewage; sewage heat exchanger;
fLanguage
English
Publisher
ieee
Conference_Titel
Electric Technology and Civil Engineering (ICETCE), 2011 International Conference on
Conference_Location
Lushan
Print_ISBN
978-1-4577-0289-1
Type
conf
DOI
10.1109/ICETCE.2011.5776257
Filename
5776257