DocumentCode
3277817
Title
Impact of Shunt-FACTS on Distance Protection of Transmission Lines
Author
Albasri, Fadhel A. ; Sidhu, T.S. ; Varma, Rajiv K.
Author_Institution
Dept. of Electr. & Comput. Eng., Univ. of Western Ontario, London, Ont.
fYear
2006
fDate
14-17 March 2006
Firstpage
249
Lastpage
256
Abstract
This paper presents the performance of distance protection of transmission lines when compensated with shunt flexible AC transmission system (FACTS) controllers/devices. The performance of distance protection is evaluated for shunt-FACTS controllers applied for mid-point voltage control. The impact of two types of shunt FACTS controllers, static VAr compensators (SVC) and static synchronous compensators (STATCOM) on the transmission line distance protection are studied for different fault types, fault locations and system conditions. The dynamics of the shunt-FACTS controllers with their associated control systems are considered and simulated using RSCAD/RTDS testing environment. The performance of both the basic/non-pilot distance scheme and a directional comparison blocking (DCB) scheme are evaluated in this paper. The results of the commercial relay testing show the adverse effects of mid-point shunt-FACTS compensation of transmission line on both non-pilot and DCB distance protection schemes
Keywords
fault location; flexible AC transmission systems; power system CAD; power system simulation; power transmission control; power transmission faults; power transmission lines; power transmission protection; static VAr compensators; voltage control; FACTS; RSCAD-RTDS simulation; STATCOM; directional comparison blocking scheme; distance protection; fault locations; fault types; mid-point voltage control; relay testing; shunt flexible AC transmission system controllers; static VAr compensators; static synchronous compensators; transmission lines; Automatic voltage control; Control system synthesis; Control systems; Fault location; Flexible AC transmission systems; Protection; Static VAr compensators; System testing; Transmission lines; Voltage control; Distance protection relay; FACTS; Power system protection; RTDS; STATCOM; SVC; Shunt compensation;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Systems Conference: Advanced Metering, Protection, Control, Communication, and Distributed Resources, 2006. PS '06
Conference_Location
Clemson, SC
Print_ISBN
0-615-13280-4
Type
conf
DOI
10.1109/PSAMP.2006.285397
Filename
4064677