• DocumentCode
    3278562
  • Title

    Partial Discharge Measurement for Cable Terminators of XLPE Power Cable

  • Author

    Apiratikul, P. ; Boonchiam, P. ; Plangklang, B. ; Suwanasri, T.

  • Author_Institution
    Department of Electrical Engineering, Rajamangala University of Technology Thanyaburi
  • fYear
    2007
  • fDate
    8-13 July 2007
  • Firstpage
    573
  • Lastpage
    576
  • Abstract
    This paper presents a partial discharge (PD) measurement for cable terminators of XLPE power cable. The power cable of rated voltage 24 kV and a cross sectional area of 240 mm2 was used in the experiment. The partial discharge level and dielectric loss are very important factors to indicate the insulation quality of power cable. Therefore, measurement techniques of partial discharge and dielectric loss are required in high voltage applications. This paper proposes a design and construction of a cable terminator by using acrylic tube. Inside of cable connector, the maximum high pressure air can be compressed more than 3 bar. In order to implement the partial discharge and the dielectric loss (tan¿) techniques, the cable terminator has to be tested according to IEC standards No.60502, No.835-3 and No.270. It can be found that the cable terminator testing gives the satisfactory and reasonably accurate results from the measurement techniques. In addition, the cost of construction is much cheaper than a commercial module.
  • Keywords
    Dielectric loss measurement; Dielectric losses; Dielectric measurements; Measurement techniques; Partial discharge measurement; Partial discharges; Power cables; Power measurement; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Solid Dielectrics, 2007. ICSD '07. IEEE International Conference on
  • Conference_Location
    Winchester, UK
  • Print_ISBN
    1-4244-0750-8
  • Electronic_ISBN
    1-4244-0751-6
  • Type

    conf

  • DOI
    10.1109/ICSD.2007.4290878
  • Filename
    4290878