• DocumentCode
    3337295
  • Title

    Verification of harmonic effects on electrical energy measurements accuracy (AMR based) in PT. PLN Distribution West Java and Banten

  • Author

    Mawardi, A. ; Purwadi, Agus ; Pranyoto, P. ; Firmansyah, M. ; Heryana, Nana ; Nurafiat, D.

  • Author_Institution
    R&D, PT.PLN, Jakarta, Indonesia
  • fYear
    2011
  • fDate
    17-19 July 2011
  • Firstpage
    1
  • Lastpage
    7
  • Abstract
    Automated meter reading system usually provided only for big customer energy metering. This paper discusses the verification of energy measurements under harmonics condition for three big customers connected to 150/70 kV high voltage and 20 kV medium voltage distribution networks of PT. PLN Distribution (a state owned electric utility company) West Java & Banten area. Harmonic effects differ substantially depending on the characteristics of the affected devices, such as metering device. The electronic energy metering system generally provided with better capability for measuring a non sinusoidal distorted current compare to previous electromechanical energy metering system due to true rms feature measurement capability. However certain periodic verification still needed to check the accuracy of AMR system installed, especially under certain harmonic load condition exposed. The verification was done by comparing the measurement results from AMR system using EDMI MK6E with the measurement results from Power Quality Meter Topaz 1000, under synchronize time for certain duration during high load and low load conditions. The comparative measurement results show that energy measured by AMR system for the three big customers are still in their accuracy class range.
  • Keywords
    distribution networks; energy measurement; power meters; power supply quality; electrical energy measurements accuracy; harmonic effects; harmonics condition; high voltage distribution networks; medium voltage distribution networks; voltage 150 kV; voltage 70 kV; Current measurement; Distortion measurement; Energy measurement; Harmonic analysis; Power measurement; Power system harmonics; Voltage measurement; amr system; energy metering; harmonic effects; power quality; total harmonic distortion; true rms;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Engineering and Informatics (ICEEI), 2011 International Conference on
  • Conference_Location
    Bandung
  • ISSN
    2155-6822
  • Print_ISBN
    978-1-4577-0753-7
  • Type

    conf

  • DOI
    10.1109/ICEEI.2011.6021691
  • Filename
    6021691