DocumentCode
3342000
Title
DC-toughened glass insulators pre-coated with RTV silicone rubber — Field returns from aged samples installed on HVDC lines
Author
Marzinotto, M. ; Lavecchia, G. ; Guarniere, M.R. ; Posati, A. ; Rebolini, M. ; George, J.-M. ; Prat, S.
Author_Institution
Terna Rete Italia-TERNA Group, Roma, Italy
fYear
2013
fDate
June 30 2013-July 4 2013
Firstpage
170
Lastpage
173
Abstract
RTV silicone rubber coating on ceramic insulators has been used for at least two decades in order to solve critical problems related to pollution in harsh environments. In Italy the experience on AC 380 kV transmission lines started ten years ago; today this kind of insulators is considered as an attractive solution to solve problems of flashovers in highly polluted areas. Recently a trial installation started on HVDC Terna´s lines. The first tests performed on an insulator string sampled after more than 2 years have shown that RTV pre-coated insulators seem to be a valid alternative to ceramic insulators in highly polluted environment even if further investigations are needed in order to better understand their behavior under DC stress.
Keywords
HVDC power transmission; ceramics; coating techniques; glass; insulators; power transmission lines; silicones; AC transmission lines; DC stress; DC-toughened glass insulator; HVDC Terna lines; HVDC lines; RTV precoated insulators; RTV silicone rubber coating; ceramic insulators; flashovers; insulator string; voltage 380 kV; Coatings; Glass; Pollution; Pollution measurement; Rubber; Surface contamination; HVDC lines; RTV coating; field experience; insulators; unified specific creepage distance;
fLanguage
English
Publisher
ieee
Conference_Titel
Solid Dielectrics (ICSD), 2013 IEEE International Conference on
Conference_Location
Bologna
ISSN
2159-1687
Print_ISBN
978-1-4799-0807-3
Type
conf
DOI
10.1109/ICSD.2013.6619772
Filename
6619772
Link To Document