Abstract
In modern power utilities attention is especially directed to the condition determination of the network´s electrical equipment, with the purpose of supporting the condition oriented asset management and maintenance strategies. In medium voltage (MV) networks, cables require the biggest investment capital. In order to point out the most suitable diagnostic parameters and their limits, a long lasting accelerated and artificial ageing experiment on MV paper insulated lead covered (PILC) cables was performed. The in this way determined dependencies of the diagnostic parameters on voltage, temperature and condition of the cables, as well as characteristic values and regarded failure probability play an immense role in the determination of cables´ condition in field measurements. Still, the diagnostic criterion (e.g. in case of dissipation losses comparison of: absolute value, hysteresis, dependency on testing voltage) could significantly influence the final diagnostic statement. In addition, the recorded values have to be evaluated regarding the composition of the cable line. This problematic will be shown in the article and discussed on several exemplar field measurements.
Keywords
ageing; asset management; condition monitoring; maintenance engineering; paper; power cable insulation; probability; MV PILC cables; MV cable lines; MV networks; MV paper-insulated lead covered cables; absolute value; accelerated ageing experiment; artificial ageing experiment; cable line composition; cable temperature; cable voltage; condition determination; condition-oriented asset management; diagnostic parameters; dissipation loss comparison; failure probability; field-measured dissipation factor values; hysteresis; interpretation approach; maintenance strategy; medium voltage networks; network electrical equipment; power utilities; testing voltage; Correlation coefficient; Dielectrics; Power cable insulation; Power cables; Temperature measurement; Voltage measurement; ageing; cable; diagnostics; dissipation factor; interpretation; mixed cable line;
fLanguage
English
Publisher
ieee
Conference_Titel
Solid Dielectrics (ICSD), 2013 IEEE International Conference on
Conference_Location
Bologna
ISSN
2159-1687
Print_ISBN
978-1-4799-0807-3
Type
conf
DOI
10.1109/ICSD.2013.6619784
Filename
6619784
Link To Document