Effect of Wind on Recirculation of Direct Air-Cooled Condenser for a Large Power Plant
Author
Zhao, Wanli ; Liu, Peiqing
Author_Institution
Moe´´s Key Lab. for Fluid Mech., Beijing Univ. of Aeronaut. & Astronauts, Beijing
fYear
2009
fDate
27-31 March 2009
Firstpage
1
Lastpage
4
Abstract
The paper introduces thermal buoyancy effects to experimental investigation of wind tunnel simulation on direct air-cooled condenser for a large power plant. Recirculation ratio of each measuring point is calculated by measuring temperature at the inlet of fans and outlet of finned tubes under different velocities and wind direction angles. The influence of wind velocity and wind direction on recirculation ratio is investigated. And the relationship between heights of wind wall and recirculation ratio under cooling tower is also discussed.
Keywords
condensers (steam plant); cooling; wind tunnels; cooling tower; direct air-cooled condenser recirculation; large power plant; recirculation ratio; thermal buoyancy effects; wind direction angles; wind tunnel simulation; wind velocity; Chemical industry; Cooling; Extraterrestrial measurements; Fans; Poles and towers; Power generation; Temperature measurement; Velocity measurement; Wind speed; Wind turbines;