Research on Lightning Overvoltage and Comprehensive Lightning Proof Measures of 10kV Overhead Insulated Distribution Lines
Author
Han Xuemin ; Mao Minghua ; Wu JianBin ; Zhou Wenjun ; Yu Jianhui ; Tu Jun ; Wang Xiaofeng
Author_Institution
Anhui Caohu Power Supply Co., Caohu
fYear
2009
fDate
27-31 March 2009
Firstpage
1
Lastpage
6
Abstract
By calculating the amplitudes of the lightning induced overvoltage and induced current of the overhead insulated distribution lines, this paper studies the damage to the lines caused by induced overvoltage and induced current. According to the calculations, the value of induced overvoltage can be 400 kV and more, greater than overhead insulated lines and obtains the optimal parameters to prevent lightning strike break by adopting insulating cross arms. In the meantime, combining the theoretical analysis, it is known that adopting 400 mm insulating cross arms can prevent lightning break. As a result, depending on different operations and considering comprehensively, this paper puts forward measures as insulating cross arms, the stab type arc protection hardware, lightning proof post insulators and lightning arresters to prevent lightning break.
Keywords
arresters; lightning protection; power distribution lines; power distribution protection; power overhead lines; lightning arresters; lightning induced overvoltage; lightning overvoltage; lightning proof post insulators; lightning strike break; overhead insulated distribution lines; overhead insulated lines; Arm; Arresters; Conductors; Flashover; Frequency; Hardware; Insulation; Lightning; Protection; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference, 2009. APPEEC 2009. Asia-Pacific
Conference_Location
Wuhan
Print_ISBN
978-1-4244-2486-3
Electronic_ISBN
978-1-4244-2487-0
Type
conf
DOI
10.1109/APPEEC.2009.4918693
Filename
4918693
Link To Document