    Research on Method to Get Corona Inception Electric-Field Intensity Based on Small Corona Cage

  • Author

    Ren Lei-Jian ; Liu Yun-Peng ; Lu Jie ; Yu Tao

  • Author_Institution
    Electr. Power Dept., North China Electr. Power Univ., Baoding
  • fYear
    2009
  • fDate
    27-31 March 2009
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Corona is an important aspect which influences the design of transmission lines and electric equipments. With the increase of altitude and voltage grade, the corona performance of equipments becomes more complex. First, this paper explains electric field distribution around the overhead multiple conductors is consistent to one of multiple conductors in the corona cage; then according to the test data of four different altitude points, we bring up the method to get corona inception electric-field intensity: in AC dry condition, using the tangent method ; in AC rain condition, using the threshold method. And afford the engineering basis to construct EHV and UHV AC project in the west high altitude area.
  • Keywords
    corona; high-voltage techniques; multiconductor transmission lines; overhead line conductors; power overhead lines; AC dry condition; AC rain condition; EHV AC project; UHV AC project; corona cage; corona inception electric-field intensity; electric equipment; electric field distribution; overhead multiple conductor; tangent method; threshold method; transmission line design; Conductors; Corona; Instruments; Loss measurement; Nonuniform electric fields; Optical losses; Optical surface waves; Power transmission lines; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference, 2009. APPEEC 2009. Asia-Pacific
  • Conference_Location
    Wuhan
  • Print_ISBN
    978-1-4244-2486-3
  • Electronic_ISBN
    978-1-4244-2487-0
  • Type

    conf

  • DOI
    10.1109/APPEEC.2009.4918697
  • Filename
    4918697