• DocumentCode
    3392478
  • Title

    The Growth of Electrical Tree and Its PD in Inner and Outer Layer of 110kV XLPE Cable Insulation

  • Author

    Wei Wang ; Heng Sui ; YanLong Yu ; Yankun Wu ; Guanghui Chen

  • Author_Institution
    State Key Lab. of Alternate Electr. Power Syst. with Renewable Energy Sources, North China Electr. Power Univ., Beijing, China
  • fYear
    2012
  • fDate
    27-29 March 2012
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    The growth of electrical tree in inner and outer layer of 110kV XLPE cable insulation was observed and its partial discharge was detected online. Because of the production process of XLPE cable, there are differences of the growth of electrical tree inside and outside the cable insulation with different voltages. Electrical trees in inner layer of insulation have bigger growth rate than the outer. With higher voltage, the situation is more obviously. When 9kV and 12kV added, there is a stage of PD disappeared before breakdown occurred, but PD persistence with 18kV and there are different changes in inner and outer layer of cable insulation.
  • Keywords
    XLPE insulation; cable insulation; partial discharges; trees (electrical); PD; XLPE cable insulation; breakdown; electrical tree growth; partial discharge; production process; voltage 110 kV; voltage 12 kV; voltage 18 kV; voltage 9 kV; Partial discharges; Power cable insulation; Power cables; Vegetation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
  • Conference_Location
    Shanghai
  • ISSN
    2157-4839
  • Print_ISBN
    978-1-4577-0545-8
  • Type

    conf

  • DOI
    10.1109/APPEEC.2012.6307327
  • Filename