• DocumentCode
    3393002
  • Title

    A Fault Locating Algorithm for the Resonant Grounding System Based on the Parameter Identification under Charge Transient

  • Author

    Zhang Shu ; Shang Wu-jun ; He Zheng-you

  • Author_Institution
    Sch. of Electr. Eng., Southwest Jiaotong Univ., Chengdu, China
  • fYear
    2012
  • fDate
    27-29 March 2012
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Aim at the problem of single-phase ground fault for resonant grounding system (that is, arc-suppression coil grounded distribution network), a fault location algorithm based on parameter identification in the charging transient is proposed in this paper. The method uses charge transient electrical quantity generated at the moment of a single-phase ground fault occurs to identify line parameters, and takes the fault location considering that the total inductance between the bus and the fault is proportional to the distance. In a 35kV model of resonant grounding system, the efficiency is verified by simulation, with different fault distance, different fault time.
  • Keywords
    earthing; fault location; power distribution faults; arc-suppression coil grounded distribution network; charge transient electrical quantity; fault distance; fault locating algorithm; fault time; line parameter identification; parameter identification; resonant grounding system; single-phase ground fault; voltage 35 kV; Circuit faults; Fault location; Grounding; Inductance; Resistance; Transient analysis;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
  • Conference_Location
    Shanghai
  • ISSN
    2157-4839
  • Print_ISBN
    978-1-4577-0545-8
  • Type

    conf

  • DOI
    10.1109/APPEEC.2012.6307356
  • Filename
    6307356