DocumentCode
3415469
Title
VLF testing and diagnosis on medium voltage power cables
Author
Mohaupt, Peter ; Baur, Martin ; Schlick, Timo
Author_Institution
BAUR Pruf- und Messtechnik GmbH, Sulz, Austria
fYear
2003
fDate
6-10 April 2003
Firstpage
202
Lastpage
209
Abstract
The advantages on VLF (very low frequency) on site testing compared to conventional testing at power frequency are shown in practical and dielectrical aspects. Furthermore VLF test voltages enable the possibility of diagnosis on site. The two well established diagnosis methods, dissipation factor (DF) measurement and partial discharge (PD) measurement are explained. Where the DF diagnosis gives a tool for judgement of the ageing status especially of plastic cables, the PD diagnosis enables detection of single defects within a cable system. The economic advantages of diagnosis are shown in practical examples. An outlook for application on VLF high voltage on site test systems concludes the paper.
Keywords
XLPE insulation; insulation testing; partial discharge measurement; power cable insulation; power cable testing; PE insulation; VLF diagnosis; VLF test voltages; VLF testing; XLPE insulation; ageing; dielectric aspects; dissipation factor measurement; medium voltage power cables; partial discharge measurement; plastic cables; power frequency; single defects detection; Aging; Dielectric measurements; Frequency; Medium voltage; Partial discharge measurement; Partial discharges; Plastics; Power cables; Power generation economics; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Construction, Operation and Live-Line Maintenance, 2003. 2003 IEEE ESMO. 2003 IEEE 10th International Conference on
Print_ISBN
0-7803-7917-9
Type
conf
DOI
10.1109/TDCLLM.2003.1196487
Filename
1196487
Link To Document