DocumentCode
3447492
Title
Reactive Power Ancillary Service from Wind Farms
Author
Ullah, Nayeem Rahmat ; Bhattacharya, Kankar ; Thiringer, Torbjörn
fYear
2007
fDate
25-26 Oct. 2007
Firstpage
562
Lastpage
567
Abstract
Reactive power/voltage control support, temporary primary frequency control support, power oscillation damping support are some of the functions that can be provided by modern wind farms (WFs) equipped with variable speed wind turbines (VSWT) with power electronic converters. This paper examines the possibility of WFs providing reactive power support to the grid system as part of ancillary service provisions. Detailed analysis of the WF capability curve is carried out, and a reactive power cost model is developed for wind turbine generators that can help the market operator or the independent system operator (ISO) in managing the system and the grid efficiently. The Cigre-32 bus test system is used to demonstrate a case study showing a 24-hour calculation of 10-minute average system operation cost considering the incoming wind energy.
Keywords
Costs; Damping; Frequency control; Power electronics; Power system modeling; Reactive power; Reactive power control; Voltage control; Wind farms; Wind turbines; Reactive power; ancillary service; variable speed wind turbine; voltage source converter;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Power Conference, 2007. EPC 2007. IEEE Canada
Conference_Location
Montreal, QC, Canada
Print_ISBN
978-1-4244-1444-4
Electronic_ISBN
978-1-4244-1445-1
Type
conf
DOI
10.1109/EPC.2007.4520393
Filename
4520393
Link To Document