  • Title

    SF6-free 550 kV combined optical voltage and current transducer system

  • Author

    Rahmatian, Farnoosh ; Chavez, Patrick P.

  • Author_Institution
    NxtPhase Corp., Vancouver, BC, Canada
  • Volume
    1
  • fYear
    2003
  • fDate
    7-12 Sept. 2003
  • Firstpage
    379
  • Abstract
    A three-phase optical voltage and current transducer system (NXVCT) for accurate metering of a 550 kV power transmission line is described. Extensive laboratory tests were performed on these units. Accuracy tests on the optical voltage transducers (OVTs) show compliance with IEC 0.1% class requirements with respect to linearity over the extended dynamic range of 10%-150% rated voltage, and with respect to accuracy over temperature, from -40 °C to +60 °C. The NXVCTs also passed a series of standard high-voltage type and routine tests, including one-minute AC withstand at 800 kV, lightning impulse tests at 1800 kV, chopped impulses at 2070 kV, wet switching impulses at 1250 kV, and RIV tests. This NXVCT system is now installed in a 500 kV substation.
  • Keywords
    electric current measurement; optical sensors; power system measurement; power transmission lines; substations; transducers; voltage measurement; -40 to 60 C; 1250 kV; 1800 kV; 2070 kV; 500 kV; 550 kV; 800 kV; current transducer system; optical voltage system; optical voltage transducers; power transmission line; Dynamic range; IEC; Impulse testing; Laboratories; Linearity; Performance evaluation; Power transmission lines; Temperature distribution; Transducers; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exposition, 2003 IEEE PES
  • Print_ISBN
    0-7803-8110-6
  • Type

    conf

  • DOI
    10.1109/TDC.2003.1335252
  • Filename
    1335252