DocumentCode
3460861
Title
Examination progress and development of HVDC power feeding system
Author
Babasaki, Tadatoshi ; Tanaka, Toshimitsu ; Asakura, Kaoru ; Nozaki, Yousuke ; Kurokawa, Fujio
Author_Institution
NTT Energy & Environ. Syst. Labs., Tokyo, Japan
fYear
2010
fDate
21-24 June 2010
Firstpage
870
Lastpage
873
Abstract
A higher voltage direct-current (HVDC) power feeding system for data centers has many advantages and is presently being studied in many countries. This system is composed of a rectifier, power distribution cabinet (PDC), batteries, and ICT equipment, and the configuration is similar to a -48-V DC power feeding system. The power feeding voltage is about 400 V. We developed a prototype of an HVDC power feeding system using commercial fuses in 2008. A prototype of a power distribution cabinet and fuses were developed in 2009. We conducted a basic experiment and confirmed that the characteristics of our prototype are stable. In this paper, we describe the advantages and development of an HVDC power feeding system and the examination progress of standardization.
Keywords
HVDC power transmission; computer centres; HVDC power feeding system; ICT equipment; batteries; data centers; fuses; higher voltage direct-current power feeding system; power distribution cabinet; rectifier; voltage -48 V; HVDC transmission; Data center; Direct Current; Higher Voltage; power feeding system;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics Conference (IPEC), 2010 International
Conference_Location
Sapporo
Print_ISBN
978-1-4244-5394-8
Type
conf
DOI
10.1109/IPEC.2010.5543343
Filename
5543343
Link To Document