DocumentCode
3467208
Title
Conduction through surface films on aluminum wire
Author
Aronstein, Jesse ; Hare, Thomas K.
fYear
1988
fDate
26-29 Sept. 1988
Firstpage
173
Lastpage
178
Abstract
Conduction through undisturbed surface films on commercial aluminum wire is experimentally evaluated by establishing an area of contact on the wire surface without applying mechanical pressure, using a conductive silver epoxy. The measurements indicate the film conduction is substantially higher than has been estimated on the basis of the properties of pure aluminum oxide. Using applied electrical conditions similar to those of building wire applications, the potential drop is measured to be the same magnitude as is observed in failing aluminum wire connections. The results show that the behavior of failing aluminum connections can be accounted for by the conduction and breakdown properties of the surface film, in the absence of mechanically induced metallic asperity junctions.<>
Keywords
aluminium; aluminium compounds; building wiring; electrical contacts; reliability; wires (electric); area of contact; building wire; commercial Al wire; conductive Ag filled epoxy; failing Al connections; film conduction; impure Al/sub 2/O/sub 3/ film; potential drop; undisturbed surface films; wire connections; Aluminum; Cable insulation; Conducting materials; Conductive films; Conductors; Impurities; Metal-insulator structures; Surface cracks; Surface resistance; Wire;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Contacts, 1988., Proceedings of the Thirty Fourth Meeting of the IEEE Holm Conference on
Conference_Location
San Francisco, CA, USA
Type
conf
DOI
10.1109/HOLM.1988.16113