• DocumentCode
    3467208
  • Title

    Conduction through surface films on aluminum wire

  • Author

    Aronstein, Jesse ; Hare, Thomas K.

  • fYear
    1988
  • fDate
    26-29 Sept. 1988
  • Firstpage
    173
  • Lastpage
    178
  • Abstract
    Conduction through undisturbed surface films on commercial aluminum wire is experimentally evaluated by establishing an area of contact on the wire surface without applying mechanical pressure, using a conductive silver epoxy. The measurements indicate the film conduction is substantially higher than has been estimated on the basis of the properties of pure aluminum oxide. Using applied electrical conditions similar to those of building wire applications, the potential drop is measured to be the same magnitude as is observed in failing aluminum wire connections. The results show that the behavior of failing aluminum connections can be accounted for by the conduction and breakdown properties of the surface film, in the absence of mechanically induced metallic asperity junctions.<>
  • Keywords
    aluminium; aluminium compounds; building wiring; electrical contacts; reliability; wires (electric); area of contact; building wire; commercial Al wire; conductive Ag filled epoxy; failing Al connections; film conduction; impure Al/sub 2/O/sub 3/ film; potential drop; undisturbed surface films; wire connections; Aluminum; Cable insulation; Conducting materials; Conductive films; Conductors; Impurities; Metal-insulator structures; Surface cracks; Surface resistance; Wire;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Contacts, 1988., Proceedings of the Thirty Fourth Meeting of the IEEE Holm Conference on
  • Conference_Location
    San Francisco, CA, USA
  • Type

    conf

  • DOI
    10.1109/HOLM.1988.16113
  • Filename
    16113