Abstract
Based on the analysis of the start-up of pumped storage generator under motor circumstance, it is found out that the conventional 20 Hz injection component is influenced by the low frequency component when ground faults take place in the stator windings for static frequency converter (SFC) start-up generator. The conventional relay is just simply blocked in case mal-operation during 20 Hz working condition. To overcome the disadvantage, a novel scheme is proposed to improve grounding- resistance(R) calculation accuracy and enhance ability to limit impact of 20 Hz component from generator. The simulation results proved its effectiveness and practicability of the scheme.
Keywords
earthing; frequency convertors; hydroelectric generators; pumped-storage power stations; power injection protection scheme; pumped storage generator; static frequency converter; stator ground fault; stator windings; Circuit faults; Frequency conversion; Induction generators; Induction motors; Power generation; Protection; Rotors; Stator windings; Synchronous motors; Voltage; Grounding; injection voltage source; protection; pumped storage; windings;
fLanguage
English
Publisher
ieee
Conference_Titel
Electric Utility Deregulation and Restructuring and Power Technologies, 2008. DRPT 2008. Third International Conference on
Conference_Location
Nanjuing
Print_ISBN
978-7-900714-13-8
Electronic_ISBN
978-7-900714-13-8
Type
conf
DOI
10.1109/DRPT.2008.4523719
Filename
4523719
Link To Document