DocumentCode
347693
Title
Motor shaft voltages and bearing currents and their reduction in multi-level medium voltage PWM voltage source inverter drive applications
Author
Wang, E.
Author_Institution
GE Ind. Syst., Salem, VA, USA
Volume
3
fYear
1999
fDate
1999
Firstpage
1602
Abstract
This paper presents test results on problems and solutions of motor shaft voltages and bearing currents in medium voltage PWM drive systems. Tests show that multi-level medium voltage PWM voltage source inverter drives can cause motor bearing currents, similar to a low voltage PWM drive, even with one motor bearing insulated. Common mode voltages generated as results of PWM switching are observed on motor windings and being capacitively coupled to the motor shaft, leading to bearing currents. Potential solutions, including altering common mode circuitry, changing grounding scheme, providing common mode filtering, and grounding motor shaft, are investigated. Test results on their effectiveness are presented
Keywords
AC motor drives; PWM invertors; machine bearings; PWM switching; bearing currents; capacitive coupling; common mode circuitry; common mode filtering; common mode voltages; grounding scheme; insulated motor bearing; medium voltage PWM drive systems; medium voltage PWM voltage source inverter; motor shaft voltages; motor windings; multi-level PWM VSI; Coupling circuits; Filtering; Grounding; Insulation; Low voltage; Medium voltage; Pulse width modulation; Pulse width modulation inverters; Shafts; System testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Industry Applications Conference, 1999. Thirty-Fourth IAS Annual Meeting. Conference Record of the 1999 IEEE
Conference_Location
Phoenix, AZ
ISSN
0197-2618
Print_ISBN
0-7803-5589-X
Type
conf
DOI
10.1109/IAS.1999.805955
Filename
805955
Link To Document