Abstract
Study on availability and reliability of electric chillers (EC) at a co-generated district cooling plant using Markov model is presented in this paper. Five years performance data were used to determine the states of the models covering the full working, partial working and failed states. State space diagram is used to indicate the possible operating scenario of the EC. The differential equations were formulated to evaluate the availability and reliability of the chilled water generated by the EC. Results from the analysis indicate that the model is able to predict the EC availability with 95 per cent confidence level in comparison with the actual data. While for the case of reliability, the values obtained by the model are comparable with the traditional binary reliability. In conclusion the developed models could be useful to predict the availability and reliability of EC at the district cooling plant.
Keywords
Markov processes; differential equations; power system reliability; refrigeration; space heating; Markov model; binary reliability; confidence level; differential equations; district cooling plant; electric chillers; failed state; full working state; multistate availability; partial working state; reliability assessment; state space diagram; Availability; Data models; Equations; Maintenance engineering; Markov processes; Predictive models; Availability; Data clustering; Markov method; reliability;
fLanguage
English
Publisher
ieee
Conference_Titel
Humanities, Science and Engineering (CHUSER), 2011 IEEE Colloquium on
Conference_Location
Penang
Print_ISBN
978-1-4673-0021-6
Type
conf
DOI
10.1109/CHUSER.2011.6163711
Filename
6163711
Link To Document