• DocumentCode
    3497317
  • Title

    Partial discharge location in power transformers using the spectra of the terminal current signals

  • Author

    Wang, Z.D. ; Crossley, P.A. ; Cornick, K.J.

  • Author_Institution
    Dept. of Electr. Eng. & Electron., Univ. of Manchester Inst. of Sci. & Technol., UK
  • Volume
    5
  • fYear
    1999
  • fDate
    1999
  • Firstpage
    58
  • Abstract
    Partial discharges (PDs) are a major source of insulation failure in a power transformer. The accurate location of the discharge is of crucial importance in on-site maintenance and repair. For power transformers operating at 132 kV and below and having a continuous disc type winding construction, a novel approach for PD location, based on a study of how PDs propagate in a transformer winding, is presented. Experimental tests are used to show that the PD source can be located using information available in the current signals measured at the transformer terminals
  • Keywords
    power transformer insulation; 132 kV; PD location; continuous disc type winding construction; insulation failure; on-site maintenance; partial discharge location; power transformers; repair; terminal current signals spectra; transformer winding;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
  • Conference_Location
    London
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-719-5
  • Type

    conf

  • DOI
    10.1049/cp:19990885
  • Filename
    818237