DocumentCode
3497317
Title
Partial discharge location in power transformers using the spectra of the terminal current signals
Author
Wang, Z.D. ; Crossley, P.A. ; Cornick, K.J.
Author_Institution
Dept. of Electr. Eng. & Electron., Univ. of Manchester Inst. of Sci. & Technol., UK
Volume
5
fYear
1999
fDate
1999
Firstpage
58
Abstract
Partial discharges (PDs) are a major source of insulation failure in a power transformer. The accurate location of the discharge is of crucial importance in on-site maintenance and repair. For power transformers operating at 132 kV and below and having a continuous disc type winding construction, a novel approach for PD location, based on a study of how PDs propagate in a transformer winding, is presented. Experimental tests are used to show that the PD source can be located using information available in the current signals measured at the transformer terminals
Keywords
power transformer insulation; 132 kV; PD location; continuous disc type winding construction; insulation failure; on-site maintenance; partial discharge location; power transformers; repair; terminal current signals spectra; transformer winding;
fLanguage
English
Publisher
iet
Conference_Titel
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location
London
ISSN
0537-9989
Print_ISBN
0-85296-719-5
Type
conf
DOI
10.1049/cp:19990885
Filename
818237
Link To Document