A sensitive method for on-site partial discharge detection on XLPE cable joints
Author
Schichler, Uwe
Author_Institution
Schering-Inst. of High Voltage Technique & Eng., Hannover Univ., Germany
Volume
2
fYear
1997
fDate
25 -30 May 1997
Firstpage
1099
Abstract
Many problems of XLPE-insulated cable systems are caused by internal defects of the joints which have to be mounted on-site. Faults arise from wrong assembly of slip-on accessories, impurities or voids. A suitable solution for a monitoring of cable joints during the after-laying test and service is a sensitive on-site partial discharge (PD) detection. This can be realized in an advantageous way with two rogowski coils, which are placed on both sides of the joint. The addition of the two wide-band measured PD signals will suppress the PD-like noise from outside the joint and only detect the PD caused within the joint
Keywords
XLPE insulation; cable jointing; insulation testing; partial discharges; power cable insulation; power cable testing; power cables; XLPE cable joint; after-laying test; fault; impurity; insulation; internal defect; on-site partial discharge detection; rogowski coil; slip-on accessory; void; Assembly; Cable insulation; Coils; Dielectrics and electrical insulation; Electric breakdown; Frequency; Monitoring; Partial discharges; Testing; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 1997., Proceedings of the 5th International Conference on
Conference_Location
Seoul
Print_ISBN
0-7803-2651-2
Type
conf
DOI
10.1109/ICPADM.1997.616639
Filename
616639
Link To Document