• DocumentCode
    3527087
  • Title

    Evaluation of steep-front overvoltage waveforms for oil-filled transformers

  • Author

    Kawashima, T. ; Okabe, Shigemitsu ; Zaima, Eiichi

  • Author_Institution
    Tokyo Electr. Power Co. Inc., Japan
  • Volume
    1
  • fYear
    1999
  • fDate
    1999
  • Firstpage
    279
  • Abstract
    Recently, steep-front overvoltages have been impressed on transformers because of changes in the layout of substations and the high-frequency characteristics of transformers. In cable-system substations, which are free from external surges, the lightning impulse withstand voltage (LIWV) of the equipment is determined by internal overvoltages such as restriking surges. It is important to investigate the insulation characteristics of oil-filled transformers under steep-front overvoltage waveforms. In this paper, based on the insulation characteristics of element models of oil-filled transformers, a method of converting steep-front overvoltage waveforms into standard lightning impulse test voltages was attempted. This method was applied to the actual analytical waveforms of restriking surges and lightning surges, then obtained the results of 7 to 27 percent decreases in peak values. This makes reduction of LIWV expected
  • Keywords
    power transformers; high-frequency characteristics; insulation characteristics; lightning impulse test voltages; lightning impulse withstand voltage; oil-filled power transformers; restriking surges; steep-front overvoltage waveforms evaluation; substations;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
  • Conference_Location
    London
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-719-5
  • Type

    conf

  • DOI
    10.1049/cp:19990561
  • Filename
    820641