• DocumentCode
    3537527
  • Title

    Development of polyethylene insulation diagnosis of high voltage cables in France

  • Author

    Clavreul, R. ; Duchateau, F.

  • Author_Institution
    Electricite de France, Moret-sur-Loing, France
  • fYear
    1995
  • fDate
    17-20 Sep 1995
  • Firstpage
    27
  • Lastpage
    30
  • Abstract
    The objective of the development of polyethylene insulation diagnosis of high voltage cables in France was first to check or to determine the origin of the damage after a dielectric breakdown and to confirm hypothesis such as an accidental water penetration in the insulation or an excess temperature rise in the cable. According to our experience gained in the operation, the main cause of the dielectric breakdown of extruded cables is water penetration in the insulation, generally in high voltage extruded cables manufactured without any waterproof screen in the sixties. Other defects correlated with an excess of the temperature rise in on-line cables can also be observed : we can note the existence of a high temperature annealing in polyethylene, or eventually a modification of the mechanical properties of the insulation. Sometimes manufactured defects, for example large cavities in the insulation, can also be detected. Finally, an evolution of the insulation could be correlated with the polyethylene ageing
  • Keywords
    ageing; annealing; electric breakdown; insulation testing; moisture; polyethylene insulation; power cable insulation; power cable testing; France; HV cables; dielectric breakdown; excess temperature rise; extruded cables; high temperature annealing; high voltage cables; insulation cavities; mechanical properties; polyethylene ageing; polyethylene insulation diagnosis; water penetration; Annealing; Breakdown voltage; Cable insulation; Dielectric breakdown; Dielectrics and electrical insulation; Manufacturing; Mechanical cables; Mechanical factors; Polyethylene; Temperature;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials, 1995. International Symposium on
  • Conference_Location
    Tokyo
  • Print_ISBN
    4-88686-047-8
  • Type

    conf

  • DOI
    10.1109/ISEIM.1995.496501
  • Filename