DocumentCode
3578546
Title
Flashover voltage of insulator string under various conditions
Author
Teo, S.Y. ; Illias, H.A. ; Mokhtar, N. ; Mokhlis, H. ; Bakar, A.H.A.
Author_Institution
Dept. of Electr. Eng., Univ. of Malaya, Kuala Lumpur, Malaysia
fYear
2014
Firstpage
119
Lastpage
122
Abstract
Porcelain insulator has been slowly replaced by composite insulator in power grid nowadays. However, flashover fault still occurs on this insulator type. Under certain conditions, partial discharges may occur on the insulator and lead to a complete flashover. The flashover can cause the breakdown and damage the whole power system. Therefore, this paper reports on the flashover voltage of 11kV composite insulator under different conditions. They are pollution methods, insulator surface condition, water content, operating orientations and the ambient temperature. It was found that the flashover voltage can be improved by using 0° operating orientation angle of the insulator, at lower temperature, dry condition, less insulator surface roughness and no pollution on the insulator. Therefore, a better understanding of flashover voltage under different pollution conditions may be attained from this work.
Keywords
flashover; partial discharges; porcelain insulators; power grids; composite insulator; flashover fault; flashover voltage; insulator surface condition; partial discharges; pollution methods; porcelain insulator; power grid; power system; voltage 11 kV; water content; Flashover; Insulators; Pollution; Rough surfaces; Surface contamination; Surface roughness; Surface treatment; Flashover; composite insulator; high voltage engineering;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy (PECon), 2014 IEEE International Conference on
Print_ISBN
978-1-4799-7296-8
Type
conf
DOI
10.1109/PECON.2014.7062425
Filename
7062425