• DocumentCode
    3601539
  • Title

    The Feasibility of Cable Sheath Fault Detection by Monitoring Sheath-to-Ground Currents at the Ends of Cross-Bonding Sections

  • Author

    Marzinotto, Massimo ; Mazzanti, Giovanni

  • Author_Institution
    TERNA, Rome, Italy
  • Volume
    51
  • Issue
    6
  • fYear
    2015
  • Firstpage
    5376
  • Lastpage
    5384
  • Abstract
    This paper aims at checking the possibility that cable sheath faults in unipolar three-phase HV and extra HV cables with sheath cross-bonding systems can be detected by monitoring sheath-to-ground currents at the solid bonding ends of major cross-bonding sections. This goal is achieved by calculating such currents for some reference case studies of faults of the outer thermoplastic jacket in unipolar three-phase land cables for power transmission in flat formation. The case studies differ as to cable voltage ratings, resistance and location of the fault, symmetry of minor sections, and number of major sections. The results show that the aforementioned possibility does exist, particularly for some fault types and for sufficiently high cable load.
  • Keywords
    cable sheathing; earthing; fault diagnosis; power cables; cable sheath fault detection; cross-bonding sections; extra HV cables; power transmission; sheath-to-ground currents; solid bonding ends; thermoplastic jacket; unipolar three-phase HV cables; Bonding; Cable shielding; Grounding; Power cables; Resistance; Solids; Underwater cables; Bonding; Fault currents; Fault location; Grounding; Power cable installation; Power cable protective covering; fault currents; fault location; grounding; power cable installation; power cable protective covering;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2015.2409802
  • Filename
    7056471