Abstract
This steel maker is upgrading the electric arc furnace (EAF) melt shop to increase production and improve metallurgical quality of their product. The increased electrical load and harmonic generation for the new furnace operation necessitated the installation of a static var compensator (SVC) to meet utility interconnect requirements. This paper describes a sequence of comprehensive analysis performed to specify the SVC including load flow analysis, flicker analysis, and harmonic analysis studies. The analysis presented in this paper sized and evaluated the proposed SVC reactive compensation to mitigate flicker, harmonics, and power factor for the new EAF and ladle melt furnace installations to comply with the utility interconnect requirements.
Keywords
arc furnaces; harmonic analysis; load flow; static VAr compensators; EAF melt shop; SVC; electric arc furnace; electrical load; flicker analysis; harmonic analysis; harmonic generation; load flow analysis; metallurgical quality; power factor; static VAr compensator; steel maker; utility interconnect requirements; Furnaces; Harmonic analysis; Power harmonic filters; Reactive power; Standards; Static VAr compensators; Steel; Electric Arc Furnace (EAF); Electric arc furnace (EAF); IEEE Std 18-1992; IEEE Std 519-1992; Ladle Melt Furnace (LMF); flicker; harmonic analysis; harmonic filtering; ladle melt furnace (LMF); static var compensator (SVC);
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.2015.2451072
Filename
7140788
Link To Document