DocumentCode
3639410
Title
Evaluation of PMU performance during transients
Author
M. Balabin;K. Görner;Y. Li;I. Naumkin;C. Rehtanz
Author_Institution
Siberian Electric Power Research Institute (branch of “
fYear
2010
Firstpage
1
Lastpage
8
Abstract
The paper presents different test methods for PMU (Phasor Measurement Unit) during transients in detail and shows practical results from tests of PMU from various vendors. The authors emphasize transients, because the measurement of stationary signals and their accuracy is already defined in IEEE C37.118. However, with the exception of step functions no dynamic signals are considered. The results are compared and advice is given for testing and evaluation of PMU measurement with dynamic signals.
Keywords
"Phasor measurement units","Transient analysis","Ethernet networks","Receivers","Synchronization","Computers","Servers"
Publisher
ieee
Conference_Titel
Power System Technology (POWERCON), 2010 International Conference on
Print_ISBN
978-1-4244-5938-4
Type
conf
DOI
10.1109/POWERCON.2010.5666079
Filename
5666079
Link To Document