• DocumentCode
    3656727
  • Title

    Implementation of reliable high-speed islanding detection, zone interlocking, and source selection schemes using smart algorithms

  • Author

    Faridul Katha Basha;Ramanathan Palaniappan;Ashok Balasubramanian;RadhaKiranMaye Anne;Michael J. Thompson;Kent L. Oliver

  • Author_Institution
    Schweitzer Engineering Laboratories, Inc., 340 Office Court, Suite D, Fairview Heights, IL 62208, USA
  • fYear
    2015
  • fDate
    5/1/2015 12:00:00 AM
  • Firstpage
    1
  • Lastpage
    12
  • Abstract
    The Valero Bill Greehey Refineries West Plant houses on-site generation and is interconnected to the utility via a looped power system. With the on-site generators not having the capacity to carry the entire plant load, this plant relies on importing power from the utility. Valero upgraded their medium-voltage protection system and was looking for a fast, deterministic, reliable, and cost-effective solution to protect their medium-voltage busbars as well as a local-area measurement-based generator islanding detection system to protect their generator equipment. An economical solution was proposed and implemented using automation controllers, which receive information from the new relays using a fiber-optic link and a protection-speed protocol. Multiple techniques on redundant hardware are used to detect the islanding condition and help improve the dependability of the islanding detection scheme, regardless of generation-load mismatch. A unique voting scheme was developed to improve security. The zone interlocked bus protection scheme programmed in the controllers uses directional information to provide high-speed selectivity during bus faults. An intelligent source selection algorithm automatically modifies the bus protection logic depending on the topology of the power system. The protection-speed processing capabilities of the automation controllers enable the high-speed operation of the schemes. This paper describes the solution implemented at Valero and introduces the algorithms developed to provide a robust integrated protection system that operates with dependability, selectivity, and security.
  • Keywords
    "Switches","Medium voltage","Communication cables","Topology","Protocols"
  • Publisher
    ieee
  • Conference_Titel
    Industrial & Commercial Power Systems Technical Conference (I&CPS), 2015 IEEE/IAS 51st
  • Type

    conf

  • DOI
    10.1109/ICPS.2015.7266416
  • Filename
    7266416