• DocumentCode
    3670056
  • Title

    Study on partial discharge pulse attenuation characteristics in 110 kV XLPE power cable

  • Author

    Xiao Gu; Bin Liu; Yang Xu; Dan Yang

  • Author_Institution
    State Key Lab. of Electr. Insulation &
  • fYear
    2015
  • fDate
    7/1/2015 12:00:00 AM
  • Firstpage
    788
  • Lastpage
    791
  • Abstract
    The attenuation characteristics of a partial discharge (PD) pulse propagating in a long-distance power cable is always a concern for PD detection. The high frequency attenuation of the symmetric PD pulse waveform has been previously well modeled, and the approximate solution concerning the asymmetric pulse has also been discussed. In this paper, a method to calculate the attenuation characteristics of the asymmetric PD calibration pulse is proposed, based on the measured attenuation constant of sinusoidal wave signals propagating in different lengths of 110 kV cross-linked polyethylene (XLPE) cables. The amplitude, pulse width, and area of the attenuated calibration pulse are measured in the field to verify the method. The results indicate that the product of the exponential function and Gaussian error function can be used to describe the attenuation characteristics of the calibration pulse, and the area under the pulse curve is unchanged.
  • Keywords
    "Power cables","Attenuation","Partial discharges","Calibration","Pulse measurements","Cable shielding","Attenuation measurement"
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials (ICPADM), 2015 IEEE 11th International Conference on the
  • Electronic_ISBN
    2160-9241
  • Type

    conf

  • DOI
    10.1109/ICPADM.2015.7295390
  • Filename
    7295390