• DocumentCode
    3674981
  • Title

    Radiometer monitoring system for partial discharge detection in substation

  • Author

    Y. Zhang;J.M. Neto;D. Upton;A. Jaber;U. Khan;B. Saeed;H. Ahmed;P. Mather;R. Atkinson;J.S. Neto;M.F. Q Vieira;P. Lazaridis;I.A. Glover

  • Author_Institution
    Department of Engineering &
  • fYear
    2015
  • fDate
    5/1/2015 12:00:00 AM
  • Firstpage
    1
  • Lastpage
    1
  • Abstract
    Progress on the development of an insulation defect detection and location system using a partial discharge (PD) wireless sensor network (WSN) will be presented. Such a PD WSN based on intensity-only measurements has cost and scalability advantages over existing detection and location technologies based on time-difference-of-arrival measurements such as described in (I. E. Portugues, P. J. Moore, I. A. Glover, IEEE Trans. on Power Delivery, 1, 2009, pp. 20–29). Figure 1 shows a hypothetical deployment of the PD WSN in an electricity substation. The (red) pentagram denotes a PD source, yellow circles and triangles denote sensor nodes, and the yellow St George´s cross denotes the data collection/processing node. Each node of the WSN is a broadband radiometer with a measurement band of 50–800 MHz, Figure 2. Three measurement sub-bands allow the radiometer to distinguish different forms of PD; in particular internal PD and corona discharge. WirelessHart has been selected as the network communications technology since this offers improved reliability over other standards (e.g. Zigbee) in harsh industrial environments.
  • Publisher
    ieee
  • Conference_Titel
    Radio Science Conference (URSI AT-RASC), 2015 1st URSI Atlantic
  • Type

    conf

  • DOI
    10.1109/URSI-AT-RASC.2015.7302823
  • Filename
    7302823