• DocumentCode
    3758742
  • Title

    Transformer economic operation control system based on zero-crossing switching

  • Author

    Sundong He;Qing Li;Renyuan Tong;Ge Shi

  • Author_Institution
    Institute of mechanical and electrical engineering, China Jiliang University, Hangzhou, China
  • fYear
    2015
  • Firstpage
    508
  • Lastpage
    512
  • Abstract
    The active power loss and reactive power loss nonlinear varied with the load, so the loss was controllable. This study built simulation experiment platform, subjects was two single-phase double winding transformer, based on method of transformer economic operation critical section. It introduced hardware and software design. Hardware circuits included electric parameters measurement circuit, AC contactor switching time measurement circuit, voltage or current zero-crossing point capture circuit and so on. Then the zero-crossing switching was put forward to reduce the transformer switching operation safety hazard. The experimental data shows load power and voltage current zero-crossing are detected exactly, AC contactor operation time was discrete, but declines with the supply voltage increasing, changes linearly. The accuracy rate, transformer economic operation and flexible switching with voltage&current zero-crossing, is 94.3%.
  • Keywords
    "Switches","Economics","Voltage measurement","Current transformers","Voltage transformers","Time measurement","Power transformers"
  • Publisher
    ieee
  • Conference_Titel
    Advanced Information Technology, Electronic and Automation Control Conference (IAEAC), 2015 IEEE
  • Print_ISBN
    978-1-4799-1979-6
  • Type

    conf

  • DOI
    10.1109/IAEAC.2015.7428605
  • Filename
    7428605