DocumentCode
3760370
Title
Diagnosis and analysis for a typical defect of partial discharge in GIS
Author
Zhumao Lu;Tianzheng Wang;Hua Yu;Jichong Liang;Yutong Chen;Dongdong Yang;Yanpeng Li
Author_Institution
State Grid Shanxi Electric Power Research Institute, Taiyuan, 030001, China
fYear
2015
Firstpage
1612
Lastpage
1616
Abstract
GIS equipment is widely used in electric power system, however, partial discharge affect the normal operation of the equipment. The paper introduces the principle of ultra-high frequency and acoustic emission partial discharge living detection methods and SF6 gas decomposition detection. And this pa per introduces typical defect cases of partial discharge in GIS equipment using different living detection method, combined with on-line monitoring. The living detection result is verified correctly after dismantlement, and analyses the reason of partial discharge. The final conclusion is that combined with ultra-high frequency on-line monitoring and a variety of living detection methods can improve the detection efficiency for insulation defects such as partial discharge in GIS equipment.
Keywords
"Partial discharges","Acoustic emission","Sulfur hexafluoride","Monitoring","Computer aided software engineering","Decision support systems"
Publisher
ieee
Conference_Titel
Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2015 5th International Conference on
Type
conf
DOI
10.1109/DRPT.2015.7432500
Filename
7432500
Link To Document