• DocumentCode
    3767093
  • Title

    Modeling and implementation of impedance based fault locator for medium transmission line

  • Author

    Adil Abdul Hameed;Ankush Gupta;AS Kiranraj; Ashwini Devendran G;P. Raja

  • Author_Institution
    Department of EEE, National Institute of Technology, Tiruchirappalli, Tamil Nadu, India
  • fYear
    2015
  • Firstpage
    111
  • Lastpage
    115
  • Abstract
    The scaled down laboratory model of the modelled line using air-core inductor and shunt capacitor has been practically designed, experimented and its performance parameters are evaluated. The protection scheme using three-step zone protection is achieved using a relay operated by an ARM Microcontroller. The Microcontroller is used as a controller which actuates the relay. This paper has been done to detect LG fault condition. The relay is so programmed that it works only when the fault occurs in within the zone and does not affect the transmission line if fault occurs outside. The ARM Microcontroller used for actuating the relay is STM 32-F4, which is programmed using IAS Embedded Workbench.
  • Keywords
    "Power transmission lines","Circuit faults","Protective relaying","Microcontrollers","Impedance","Resistance"
  • Publisher
    ieee
  • Conference_Titel
    Condition Assessment Techniques in Electrical Systems (CATCON), 2015 International Conference on
  • Type

    conf

  • DOI
    10.1109/CATCON.2015.7449518
  • Filename
    7449518