• DocumentCode
    3772443
  • Title

    Cable specimen length effects on the response of corona pulse detectors

  • Author

    R. Bartnikas;R. Morin

  • Author_Institution
    Hydro-Quebec Institute of Research, Varennes, Canada
  • fYear
    1976
  • fDate
    6/1/1976 12:00:00 AM
  • Firstpage
    76
  • Lastpage
    79
  • Abstract
    An extensive study has been carried out on the response characteristics of RCL-type corona detectors as a function of cable length, using terminated and unterminated XLPE insulated distribution power-cable specimens. The corona detection circuit response was examined both in the time and frequency domains, utilizing calibration pulse rise times between 0.1 and 20 µs. Particular attention was given to errors arising with unterminated cable specimens and the techniques on how these may be eliminated with suitable high voltage terminations. The transition between lumped circuit and distribution parameter or transmission line behavior was also considered.
  • Keywords
    "Current measurement","Power cables","Power cable insulation","Temperature measurement","Conferences"
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1976 IEEE International Conference on
  • Print_ISBN
    978-1-5090-3120-7
  • Type

    conf