Accuracy of current transformer with current errors at harmonics equal to the limiting values defined in IEC 60044-8 standard for transformation of distorted primary current
Author
Michal Kaczmarek
Author_Institution
Institute of Electrical Power Engineering, Lodz University of Technology, Lodz, Poland
fYear
2015
fDate
7/1/2015 12:00:00 AM
Firstpage
1
Lastpage
4
Abstract
Accuracy requirements at harmonics are defined for electronic current transformers in IEC 60044-8 standard. As indicated there defined limiting values of current error ensure that the contribution of harmonics measurement error would add roughly 15%, in the worst case, on the theoretical error of the corresponding power metering class accuracy. In accordance with IEC 61000-3-12 standard total harmonic distortion of current caused by emission of higher harmonics from equipment connected to public low-voltage systems may be equal to 47%. Accuracy of 0.1-1 classes measuring current transformers with current errors at harmonics equal to the limiting values defined in IEC 60044-8 standard for transformation of such a distorted primary current may decrease over 12 times in relation to accuracy designated for transformation of sinusoidal current of frequency 50 Hz for which they were designed.
Keywords
"Harmonic analysis","Power system harmonics","Harmonic distortion","Limiting","IEC Standards","Current transformers"