    PD frequency characteristics for a void bounded with LDPE

  • Author

    Kim, C.-S. ; Hirase, T. ; Mizutani, T.

  • Author_Institution
    Nagoya Univ., Japan
  • fYear
    2002
  • fDate
    2002
  • Firstpage
    712
  • Lastpage
    715
  • Abstract
    The change in PD (partial discharge) pulse shape for a void bounded with LDPE was measured using a time-resolved measurement system with an ultra-wideband detector. Phase-resolved patterns also were obtained by a conventional PD measuring system. The frequency spectrum analysis of PD pulse waveform showed that ageing stages have unique frequency distributions. PD patterns also have different frequency ranges. The frequency distribution was concluded to be applicable to the insulation diagnosis.
  • Keywords
    ageing; insulation testing; partial discharge measurement; polyethylene insulation; voids (solid); LDPE insulation diagnosis; ageing process; frequency distribution; partial discharge pulse shape; phase-resolved pattern; time-resolved measurement system; ultra-wideband detector; void defect; Aging; Detectors; Frequency; Partial discharge measurement; Partial discharges; Phase measurement; Pulse measurements; Pulse shaping methods; Shape measurement; Ultra wideband technology;