• DocumentCode
    3855467
  • Title

    Low-current fault detection in high impedance grounded distribution networks, using residual variations of asymmetries

  • Author

    K. J. Sagastabeitia;I. Zamora;A. J. Mazón;Z. Aginako;G. Buigues

  • Author_Institution
    Dept. of Electr. Eng., Univ. of the Basque Country UPV/EHU, Bilbao, Spain
  • Volume
    6
  • Issue
    12
  • fYear
    2012
  • fDate
    12/1/2012 12:00:00 AM
  • Firstpage
    1252
  • Lastpage
    1261
  • Abstract
    This paper presents a new method of detecting low-current faults in high impedance grounded distribution networks, in both compensated and ungrounded medium voltage networks. Based on monitoring the residual variations of line and phase asymmetries, the proposed algorithm can be used in combination with other steady-state data-based methodologies, in order to detect the existence of a single-phase ground fault, as well as identify the faulty feeder and phase. Although it could also be used in compensated networks by means of other techniques (such as the injection of zero-sequence currents in the neutral), the algorithm described in this paper has been developed by using superposed voltages, so as to make its application possible in compensated and ungrounded distribution networks. Furthermore, the reliability of this algorithm has been extensively tested in Matlab/Simulink, considering a wide range of resistive faults, and its practical applicability has also been described.
  • Journal_Title
    IET Generation, Transmission & Distribution
  • Publisher
    iet
  • ISSN
    1751-8687
  • Type

    jour

  • DOI
    10.1049/iet-gtd.2012.0195
  • Filename
    6403942