DocumentCode
454051
Title
Research on isolated diesel-wind power system equipped with doubly fed induction generator
Author
Qiao Jiageng ; Zongxiang, Lu ; Yong, Min
Author_Institution
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
fYear
2006
fDate
28-31 March 2006
Firstpage
246
Lastpage
250
Abstract
In this paper, we focus on a MW level diesel-wind power system consisting of a wind generator equipped with doubly fed induction generator (DFIG) and a diesel generator. Compared with the conventional diesel-wind system, the response of the system equipped with DFIG during wind fluctuation and load changes is more stable, and the ability for reactive power output of DFIG can improve the reactive power control in system operation observably. The performance of isolated diesel-wind power systems can be improved effectively by enhancing the wind generators. Analysis also shows that in this kind of system, the diesel generator terminal voltage and the upper limits for reactive power output of DFIG are important operative parameters affecting the operation performance.
Keywords
asynchronous generators; diesel-electric generators; diesel-electric power stations; hybrid power systems; reactive power; wind power plants; wind turbines; diesel generator; diesel-wind power system; doubly fed induction generator; hybrid power system; power system operation; reactive power control; wind fluctuation; wind generator; wind turbine;
fLanguage
English
Publisher
iet
Conference_Titel
AC and DC Power Transmission, 2006. ACDC 2006. The 8th IEE International Conference on
Conference_Location
IET
ISSN
0537-9989
Print_ISBN
0-86341-613-6
Type
conf
Filename
1633651
Link To Document