• DocumentCode
    473198
  • Title

    Secondary Arc Extinction and Detection Real and Simulated

  • Author

    Giesbrecht, J. ; Ouellette, D.S. ; Henville, C.F.

  • Author_Institution
    RTDS Technoligies Inc., Winnipeg, MB
  • fYear
    2008
  • fDate
    17-20 March 2008
  • Firstpage
    138
  • Lastpage
    143
  • Abstract
    Removal of a single line to ground fault by isolating only the faulted phase frequently leads to the creation of a secondary fault arc. Auto reclose protection schemes depend upon the absence of a secondary arc prior to reclosing. Consequently, there is great benefit from a technology to determine secondary arc extinction detection. The testing of SAED can be difficult and require the expense and complexity of staged system faults. A great deal of planning is necessary to do this however, and many fault scenarios cannot be fully studied. Accurate simulation of the phenomenon can alleviate many of these difficulties.
  • Keywords
    arcs (electric); power system faults; relay protection; auto reclose protection schemes; power system faults; relay response; secondary arc extinction; single line-to ground fault; testing; Atmospheric modeling; Capacitors; Circuit faults; Impedance; Mathematical model; Power transmission lines; Relays;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on
  • Conference_Location
    Glasgow
  • ISSN
    0537-9989
  • Print_ISBN
    978-0-86341-902-7
  • Type

    conf

  • Filename
    4496974