• DocumentCode
    473296
  • Title

    Practical Experinences with Faulty Feeder Indentification Using Transient Signals

  • Author

    Xue Yongduan ; Xu Bingyin ; Ma Shicong ; Wang Tao

  • Author_Institution
    Kehui Electr. Ltd., Zibo
  • fYear
    2008
  • fDate
    17-20 March 2008
  • Firstpage
    720
  • Lastpage
    723
  • Abstract
    The faulty feeder identification method for the non-effectively earthed network using transient signals is introduced. Practical field experiences with the method are presented. The transient method is proved effective in identifying the feeder with the metal and low resistance fault, while further investigation is needed to improve its high resistance performances. Analysis to the field recordings revealed some of the permanent faults have foreboding temporary faults. The transient method offers the possibility of identifying feeders with the incipient faults, which provides valuable condition monitoring information.
  • Keywords
    earthing; power distribution faults; power distribution protection; power system transients; condition monitoring information; faulty feeder identification; noneffective earthed distribution network; transient signal; Capacitance; Circuit faults; Fault diagnosis; Metals; Resistance; Substations; Transient analysis;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on
  • Conference_Location
    Glasgow
  • ISSN
    0537-9989
  • Print_ISBN
    978-0-86341-902-7
  • Type

    conf

  • Filename
    4497073