DocumentCode
473296
Title
Practical Experinences with Faulty Feeder Indentification Using Transient Signals
Author
Xue Yongduan ; Xu Bingyin ; Ma Shicong ; Wang Tao
Author_Institution
Kehui Electr. Ltd., Zibo
fYear
2008
fDate
17-20 March 2008
Firstpage
720
Lastpage
723
Abstract
The faulty feeder identification method for the non-effectively earthed network using transient signals is introduced. Practical field experiences with the method are presented. The transient method is proved effective in identifying the feeder with the metal and low resistance fault, while further investigation is needed to improve its high resistance performances. Analysis to the field recordings revealed some of the permanent faults have foreboding temporary faults. The transient method offers the possibility of identifying feeders with the incipient faults, which provides valuable condition monitoring information.
Keywords
earthing; power distribution faults; power distribution protection; power system transients; condition monitoring information; faulty feeder identification; noneffective earthed distribution network; transient signal; Capacitance; Circuit faults; Fault diagnosis; Metals; Resistance; Substations; Transient analysis;