DocumentCode
510956
Title
Discharge characteristics in short rod-plane gaps with dielectric-covered rod under lightning impulse voltages
Author
Mavroidis, P.N. ; Mikropoulos, P.N. ; Stassinopoulos, C.A. ; Dodos, A. ; Zannias, P.
Author_Institution
High Voltage Lab., Aristotle Univ. of Thessaloniki, Thessaloniki, Greece
fYear
2008
fDate
7-12 Sept. 2008
Firstpage
289
Lastpage
292
Abstract
Results are presented concerning both prebreakdown phenomena and the breakdown mechanism in short rod-plane gaps with dielectric-covered rod under positive standard lightning impulse voltages. Characteristic discharge parameters, namely first and second corona inception time and voltage, and time and voltage to breakdown were measured, through multiple level tests, with the gap length as a parameter. The simple air gaps i.e. without any insulating covers were considered as reference cases. In the presence of the dielectric cover breakdown occurs at higher applied voltages as a result of increased both corona inception voltages and discharge path. Interpretation of the results is made based on the discharge development pattern and electric field calculations.
Keywords
air gaps; corona; lightning protection; breakdown mechanism; corona inception time; corona voltage; dielectric-covered rod; electric field calculations; gap length; lightning impulse voltages; positive standard lightning impulse voltages; prebreakdown phenomena; short rod-plane gaps; Air gaps; Breakdown voltage; Corona; Dielectric breakdown; Dielectric measurements; Dielectrics and electrical insulation; Length measurement; Lightning; Testing; Time measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Gas Discharges and Their Applications, 2008. GD 2008. 17th International Conference on
Conference_Location
Cardiff
Print_ISBN
978-0-9558052-0-2
Type
conf
Filename
5379232
Link To Document